Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 18, 2022, 06:27 AM
  • 18 0488_18 1194_01172022_223634.mp4

Date
01/17/2022
W/O
931718
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00687
PipeID
P15040
Time
10:27 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9834
Sewer Name
18 LOWER SPRINGS ROAD TRUNK REPLACEMENT
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_931718_TV18109_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 1194
Downstream MH
18 0488
Dir. of Survey
Upstream
Length Surveyed
96.3 ft.
Total Length
96.3 ft.
Structural Index
3
Structural Quick
413C
Structural Rating
97
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 18 1194 to 18 0488
MH: 18 1194MH: 18 0488upstream0 ft. MGO - General Observation - STOP LOG AT MOUTH OF PIPE0 ft. MGO - General Observation - ROACHES @ MH1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.7 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES94.3 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start94.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start94.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.3 ft. MWL - Water Level, 5 %of cross sectional area96.3 ft. AMH - Downstream Manhole, Survey Begins - 18 119496.3 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (4)

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - STOP LOG AT MOUTH OF PIPE

    96.3 ft. - General Observation - STOP LOG AT MOUTH OF PIPE

  • General Observation - ROACHES @ MH

    96.3 ft. - General Observation - ROACHES @ MH

Observations (12)

DistanceCodeObservation
2FM
0MWL
94.6DAGS
2CM
96.3MGOSTOP LOG AT MOUTH OF PIPE
96.3MGOROACHES @ MH
0AMH18 1194
94.6CM
2DAGS
0MWM
2SSS
94SSS

Properties (8)

additional_info
630138011722201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-01-17T22:27:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31671