- Date
- 02/22/2022
- W/O
- 0940709
- Weather
- —
- Operator/Surveyor
- REVELES
- Sewer ID
- Z00092
- PipeID
- P08924
- Time
- 12:52 AM
- Certificate
- U11506022630
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- —
- Sewer Name
- B JOINT OUTFALL B - UNIT 5B
- City
- EAST PASDENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 03
- Purpose
- Resurvey For Any Reason
- Project
- 20200222VMR_JOINT_OUTFALL_B_UNIT_5B
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- B 0412
- Downstream MH
- B 0411
- Dir. of Survey
- Downstream
- Length Surveyed
- 284.5 ft.
- Total Length
- 284.5 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 1
- O&M Quick
- 1500
- O&M Rating
- 5
- Overall Index
- 1
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole B 0412 to B 0411 Observation photos (3)

136.5 ft. - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES

243.3 ft. - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YESR

284.5 ft. - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: YES - 10%