Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2021, 05:12 AM
  • 15 0083_15 0082_11032021_214018.mp4

Date
11/03/2021
W/O
921812
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00633
PipeID
P21848
Time
10:12 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9482
Sewer Name
15 TURNBULL CANYON TRUNK
City
CITY OF INDUSTRY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_921812_TV15032_NOV2021
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0083
Downstream MH
15 0082
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 0083 to 15 0082
MH: 15 0083MH: 15 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0083, NW SIPHON0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S NW SIPHON.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

Observation photos (2)

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S NW SIPHON.

    2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S NW SIPHON.

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
0AMH15 0083, NW SIPHON
0MWL
0MWM
2MSAVIEW OF DOWNLEG OF U/S NW SIPHON.
2DAGS

Properties (7)

additional_info
630069110321201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-11-03T22:12:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false