Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 06:41 AM
  • 15 0087_15 0086_11012021_224612.mp4

Date
11/01/2021
W/O
921812
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00633
PipeID
P12000
Time
11:41 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9481
Sewer Name
15 TURNBULL CANYON TRUNK
City
HACIENDA HEIGHTS
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_921812_TV15032_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0087
Downstream MH
15 0086
Dir. of Survey
Downstream
Length Surveyed
68.6 ft.
Total Length
68.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412D
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
54
Pipe schematic from manhole 15 0087 to 15 0086
MH: 15 0087MH: 15 0086downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 00870 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS64.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish66.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish68.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK68.6 ft. AMH - Downstream Manhole, Survey Ends - 15 008668.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    68.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
66.9DSZ
68.6MGOCONNECTION AT MH 3 O'CLOCK
68.6AMH15 0086
0AMH15 0087
5.7DSZDEBRIS
68.6MGOCOCKROACHES IN MANHOLE
2DAGS
0MWM
66.9DAGS
64.4TFC
0MWL

Properties (6)

additional_info
630069110121202
custom_field_two
4
customer
1
datetime
2021-11-01T23:41:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false