Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 06:46 AM
  • 15 0086_15 0085_11012021_225346.mp4

Date
11/01/2021
W/O
921812
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00633
PipeID
P11999
Time
11:46 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9481
Sewer Name
15 TURNBULL CANYON TRUNK
City
HACIENDA HEIGHTS
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_921812_TV15032_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0086
Downstream MH
15 0085
Dir. of Survey
Downstream
Length Surveyed
204.2 ft.
Total Length
204.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412G
O&M Rating
84
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 15 0086 to 15 0085
MH: 15 0086MH: 15 0085downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 00862 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start73.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish204.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE204.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0085

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    204.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
2DAGS
0MWM
0MWL
0MGOCOCKROACHES IN MANHOLE
0MGOCONNECTION AT MH 3 O'CLOCK
73.1TFC
202.3DAGS
0AMH15 0086
204.2MGOCOCKROACHES IN MANHOLE
204.2AMH15 0085
124.8TF
191.3TFC

Properties (7)

additional_info
630069110121202
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-11-01T23:46:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false