Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 06:53 AM
  • 15 0085_15 0084_11012021_230401.mp4

Date
11/01/2021
W/O
921812
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00633
PipeID
P11998
Time
11:53 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9481
Sewer Name
15 TURNBULL CANYON TRUNK
City
HACIENDA HEIGHTS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_921812_TV15032_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0085
Downstream MH
15 0084
Dir. of Survey
Downstream
Length Surveyed
251.9 ft.
Total Length
251.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
412O
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
166
Pipe schematic from manhole 15 0085 to 15 0084
MH: 15 0085MH: 15 0084downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 00850 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start110.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS116.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES190.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES241.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish249.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish251.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0084251.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE251.9 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 4 O' CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    116.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    190.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    251.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
110.2DSZDEBRIS
2DAGS
251.9AMH15 0084
251.9MGOCOCKROACHES IN MANHOLE
116.6CM
249.6DAGS
0AMH15 0085
251.9MGOCONNECTIONS IN MH AT BOTH 3 AND 4 O' CLOCK
0MWM
0MWL
241.8TF
249.6DSZ
190.1CM

Properties (7)

additional_info
630069110121202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-01T23:53:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false