Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 09:08 AM
  • 05 0140_05 0139_12232021_012002.mp4

Date
12/23/2021
W/O
926779
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05432
Time
1:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9569
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_926779_TV05373_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
27 in.
Upstream MH
05 0140
Downstream MH
05 0139
Dir. of Survey
Downstream
Length Surveyed
313.3 ft.
Total Length
313.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 05 0140 to 05 0139
MH: 05 0140MH: 05 0139downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01402.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COAT311.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish313.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0139

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2.5SAP
0MWM
313.3AMH05 0139
2.5MGOMAG COAT
0MWL
0AMH05 0140
311.5SAP

Properties (7)

additional_info
630074122221201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-12-23T01:08:17-08:00
documentation
PROPIPE
is_lateral_inspection
false