Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 06:51 AM
  • 05 0097_05 0096_12222021_230427.mp4

Date
12/22/2021
W/O
926779
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05387
Time
10:51 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9569
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_926779_TV05373_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
05 0097
Downstream MH
05 0096
Dir. of Survey
Downstream
Length Surveyed
326.5 ft.
Total Length
326.5 ft.
Structural Index
3
Structural Quick
533L
Structural Rating
207
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
207
Pipe schematic from manhole 05 0097 to 05 0096
MH: 05 0097MH: 05 0096downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 00970 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area2.3 ft. MGO - General Observation - MAG COAT2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start58.6 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO67.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.9 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO296.9 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO313.7 ft. MGO - General Observation - SURFACE SPALLING - 8 TO 4 O'CLOCK.323.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK326.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0096326.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    58.6 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    67.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    275.9 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    296.9 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

Observations (16)

DistanceCodeObservation
326.5MGOCONNECTION AT THE MH 9 OC'LOCK
275.9SRV
323.5SAP
0MWM
313.7MGOSURFACE SPALLING - 8 TO 4 O'CLOCK.
2.3MGOMAG COAT
296.9SRV
0AMH05 0097
326.5AMH05 0096
326.5MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
0MGOCONNECTION AT THE MH 9 OC'LOCK
2.3SAV
67.6SAP
67.6SAV
58.6SRV
0MWL

Properties (7)

additional_info
630074122221201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-12-22T22:51:02-08:00
documentation
PROPIPE
is_lateral_inspection
false