Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 07:04 AM
  • 05 0096_05 0095_12222021_232703.mp4

Date
12/22/2021
W/O
926779
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05386
Time
11:04 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9569
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_926779_TV05373_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
18 in.
Upstream MH
05 0096
Downstream MH
05 0095
Dir. of Survey
Downstream
Length Surveyed
333 ft.
Total Length
333 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 05 0096 to 05 0095
MH: 05 0096MH: 05 0095downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 05 00960 ft. MWL - Water Level, 20 %of cross sectional area2.7 ft. MGO - General Observation - MAG COAT2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16 ft. MGO - General Observation - POSSIBLE VISIBLE REINFORCEMENT @ 11 O'CLOCK146 ft. MGO - General Observation - @ 2 O'CLOCK, POSSIBLE VISIBLE REINFORCEMENT AND IN THIS VICINITY (8 TO 4 O'CLOCK).222 ft. MGO - General Observation - SPALLING @ 2 TO 3 O'CLOCK.331.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333 ft. AMH - Downstream Manhole, Survey Ends - 05 0095333 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
331.5SAP
0MGOCONNECTION AT THE MH 9 OC'LOCK
146MGO@ 2 O'CLOCK, POSSIBLE VISIBLE REINFORCEMENT AND IN THIS VICINITY (8 TO 4 O'CLOCK).
333AMH05 0095
333MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
2.7MGOMAG COAT
222MGOSPALLING @ 2 TO 3 O'CLOCK.
0MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
16MGOPOSSIBLE VISIBLE REINFORCEMENT @ 11 O'CLOCK
0AMH05 0096
2.8SAP
0MWL

Properties (7)

additional_info
630074122221201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2021-12-22T23:04:58-08:00
documentation
PROPIPE
is_lateral_inspection
false