Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2022, 10:51 AM
  • 18 0491_18 0490_292022_025700.mp4

Date
02/09/2022
W/O
0931911
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14345
Time
2:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3009
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20220209MDM_NORTH_PLANT_OUtFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0491
Downstream MH
18 0490
Dir. of Survey
Downstream
Length Surveyed
710.7 ft.
Total Length
710.7 ft.
Structural Index
2
Structural Quick
5241
Structural Rating
235
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
235
Pipe schematic from manhole 18 0491 to 18 0490
MH: 18 0491MH: 18 0490downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:25AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active17.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE30.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H35.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H45.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H52.7 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - H55 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT67.8 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL72.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL72.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL75.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, - SL75.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, - SL75.2 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE JOINT TO JOINT LONGER82.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL82.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H84.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL85.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H87.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL87.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H87.4 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET INSET CIRCUM FRACTURE88.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H89.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL92.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - H93.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H97.8 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL98.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL100.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL103 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H103.5 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL109.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish109.8 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Finish - OFFSET LONG FRACTURE120.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H124.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H130.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H143.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H151.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H156 ft. RPP - Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - CONCRETE156 ft. MGO - General Observation - PATCH REPAIR 12:00156.4 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL156.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL156.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL160.8 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES163.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H166.5 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H169.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - H171.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H174.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H176.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H206.6 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H213.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H234.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H234.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H247.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H251.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H259.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES304.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL322.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL322.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT322.6 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE OFFSET325.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H325.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT325.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H325.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL329.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL331.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H345.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL358.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H362.1 ft. RPP - Repair Patch, from 08 to 04 o'clock, within 8 inches of joint: YES - CONCRETE INCASEMENT JOINT TO JOINT365.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL367.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL376.1 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL379.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL380.9 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start - SL383.9 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish - SL393.3 ft. MGO - General Observation - BROKEN PIPE 12:00 LONG FRACTURE400.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE407.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES408.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL411.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT415.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT415.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H429.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped430.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H430.5 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - OFFSET SLIGHT FRACTURE430.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL443.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL443.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped448.6 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL453.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H462 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL462 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H468.8 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL473.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL476.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H476.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start - H493.5 ft. B - Broken, at 12 o'clock, within 8 inches of joint: NO - 12:00 SLIGHT FRACTURE512.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL517.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped524.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL530.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - H530.6 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT FRACTURE OFFSET530.6 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Finish - H539.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H558.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL566.8 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H569 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H569 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL571.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL573.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL573.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H578.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H578.5 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE589.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H595.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H644.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H644.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL644.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H644.5 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Finish - OFFSET LONG SLIGHT FRACTURE649 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL659.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - OUTER SURFACE664.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL666.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL710.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL710.7 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observation photos (31)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    72.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES,  - SL

    75.2 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, - SL

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES,  - SL

    75.2 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, - SL

  • Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE JOINT TO JOINT LONGER

    75.2 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE JOINT TO JOINT LONGER

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H

    87.4 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET INSET CIRCUM FRACTURE

    87.4 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET INSET CIRCUM FRACTURE

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

    88.3 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

  • Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - CONCRETE

    156 ft. - Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - CONCRETE

  • General Observation - PATCH REPAIR 12:00

    156 ft. - General Observation - PATCH REPAIR 12:00

  • Broken, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE OFFSET

    322.6 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE OFFSET

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

    325.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

    325.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

    325.2 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

  • Repair Patch, from 08 to 04 o'clock, within 8 inches of joint: YES - CONCRETE INCASEMENT JOINT TO JOINT

    362.1 ft. - Repair Patch, from 08 to 04 o'clock, within 8 inches of joint: YES - CONCRETE INCASEMENT JOINT TO JOINT

  • Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL

    376.1 ft. - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start - SL

    380.9 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start - SL

  • General Observation - BROKEN PIPE 12:00 LONG FRACTURE

    393.3 ft. - General Observation - BROKEN PIPE 12:00 LONG FRACTURE

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

    400.6 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    408.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    415.6 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - OFFSET SLIGHT FRACTURE

    430.5 ft. - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - OFFSET SLIGHT FRACTURE

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL

    443.1 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H

    476.2 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start - H

    476.2 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start - H

  • Broken, at 12 o'clock, within 8 inches of joint: NO - 12:00 SLIGHT FRACTURE

    493.5 ft. - Broken, at 12 o'clock, within 8 inches of joint: NO - 12:00 SLIGHT FRACTURE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    558.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

    573.8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

    578.4 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

  • Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE

    578.5 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES, Start - OFFSET LONG FRACTURE

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - OUTER SURFACE

    659.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - OUTER SURFACE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    664.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

Observations (127)

DistanceCodeObservation
124.2FLH
468.8FCSL
325.2FLSLIGHT
160.8FL
571.5FCSL
325.2FCH
72.6FCSL
82.9FCSL
379.7FCSL
0MWL
517.3TBCapped
476.2FLH
362.1RPPCONCRETE INCASEMENT JOINT TO JOINT
443.1FCSL
569FLH
30.2FLH
415.6FLSLIGHT
322.6FCSL
530.6FLH
17.2FCHAIRLINE
103.5FCSL
97.8FCSL
365.3FCSL
367.8FCSL
666.1FCSL
512.9FCSL
259.8FL
234.7FLH
644.4FLH
345.2FCSL
473.7FCSL
156.9FCSL
448.6FCSL
0AMH3:25AM
109.8FL
325.1FLH
476.2FLH
52.7FCH
569FCSL
251.6FLH
163.7FLH
156RPPCONCRETE
589.2FCH
649FCSL
539.1FCH
75.2FLSL
322.6FLSLIGHT
393.3MGOBROKEN PIPE 12:00 LONG FRACTURE
103FLH
84.2FCSL
130.5FLH
82.9FCH
578.5BOFFSET LONG FRACTURE
35.1FCH
429.7TFCCapped
383.9FLSL
234.7FLH
322.6BSLIGHT FRACTURE OFFSET
573.8FCSL
462FLSL
156MGOPATCH REPAIR 12:00
55FCSLIGHT
100.2FCSL
206.6FCH
72.6FLSL
415.6FLH
329.6FCSL
430.5BOFFSET SLIGHT FRACTURE
109.8BOFFSET LONG FRACTURE
376.1FCSL
659.7SSSOUTER SURFACE
644.5FLH
304.9FLSL
98.7FCSL
0MWM
156.4FCSL
710.1FLSL
45.4FCH
0MGOConn. @ Mh, 9 O' Clock. Active
595.6FLH
558.7FLSL
380.9FLSL
213.2FLH
151.4FLH
156.4FCSL
174.1FLH
411.9FCSLIGHT
89.9FCSL
566.8FCH
120.4FLH
524.1FCSL
87.4FCSL
443.1TFCCapped
93.7FCH
530.6BSLIGHT FRACTURE OFFSET
247.2FLH
573.8FLH
407.3FC
358.4FCH
88.3FLH
430.4FCH
176.7FCH
143.2FCH
530.6FLH
710.7AMH5:20AM
644.5BOFFSET LONG SLIGHT FRACTURE
453.3FCH
87.4FLH
462FLH
75.2FLSL
169.1FLH
166.5FCH
578.4FLH
430.5FCSL
87.4BOFFSET INSET CIRCUM FRACTURE
325.2FLSL
171.5FLH
664.4FLSL
85.2FLH
408.2FMSL
92.6FLH
75.2BOFFSET LONG FRACTURE JOINT TO JOINT LONGER
493.5B12:00 SLIGHT FRACTURE
400.6FCMODERATE
644.4FLSL
331.7FCH
67.8FCSL

Properties (6)

custom_field_three
BROKEN PIPE THROUGHOUT REACH
custom_field_two
1
customer
LACSD
datetime
2022-02-09T02:51:05-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false