Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2021, 03:58 PM
  • 29 0739_29 0738_12232021_081910.mp4

Date
12/23/2021
W/O
931720
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00527
PipeID
P24245
Time
7:58 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9705
Sewer Name
29 ALAMITOS PUMPING PLANT TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931720_TV29078_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0739
Downstream MH
29 0738
Dir. of Survey
Downstream
Length Surveyed
320.4 ft.
Total Length
320.4 ft.
Structural Index
3
Structural Quick
4F3L
Structural Rating
332
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
332
Pipe schematic from manhole 29 0739 to 29 0738
MH: 29 0739MH: 29 0738downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 07392 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - PIPE IS NRCP31.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES50.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"68.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"114.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"127.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"141.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start168.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"181 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"197.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"216.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"239.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"270.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"298.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"316.1 ft. MMC - Material Change, Vitrified clay pipe316.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"320.4 ft. AMH - Downstream Manhole, Survey Ends - 29 0738

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - PIPE IS NRCP

    2 ft. - General Observation - PIPE IS NRCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    31.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    50.2 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    141.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    197.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Material Change, Vitrified clay pipe

    316.1 ft. - Material Change, Vitrified clay pipe

Observations (24)

DistanceCodeObservation
50.2TBA
127.5TF
298.3TF
316.1MMC
114.7TF
197.3TB
316.1FM
270.3TF
68.5TF
141.6FM
320.4AMH29 0738
0MWM
2SAP
181TF
216.9TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
317.1TF
0AMH29 0739
239.7TF
168.3TF
316.1SAP
2MGOPIPE IS NRCP
31.4FL

Properties (7)

additional_info
630074122321061
custom_field_three
AGGREGATE PROJECTING ,FRACTURES
custom_field_two
3
customer
1
datetime
2021-12-23T07:58:37-08:00
documentation
PRO PIPE
is_lateral_inspection
false