Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 18, 2022, 11:43 AM
  • 18 0456_18 0455_01182022_040416.mp4

Date
01/18/2022
W/O
931504
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00691
PipeID
P14308
Time
3:43 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9836
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_931504_TV18140_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0456
Downstream MH
18 0455
Dir. of Survey
Downstream
Length Surveyed
478 ft.
Total Length
478 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0456 to 18 0455
MH: 18 0456MH: 18 0455downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04560 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT231.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"277.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"413.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS429.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"475.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish475.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish475.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"475.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish478 ft. AMH - Downstream Manhole, Survey Ends - 18 0455478 ft. MGO - General Observation - COCKROACHES IN MH478 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 10 O'CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • General Observation - COCKROACHES IN MH

    478 ft. - General Observation - COCKROACHES IN MH

Observations (18)

DistanceCodeObservation
231.9TBA
0AMH18 0456
0MWL
475.8DAGS
478AMH18 0455
2DAGS
429.9TBA
475.8SAP
0MGOCOCKROACHES IN MH
2SAP
413.2DSZDEBRIS
478MGOCOCKROACHES IN MH
475.8TFA
0MWM
478MGOACTIVE CONNECTION AT MH 10 O'CLOCK
2MGOMAG COAT
475.8DSZ
277.1TBA

Properties (7)

additional_info
630138011722203
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2022-01-18T03:43:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false