Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2022, 08:12 AM
  • H 1288_H 1287_01142022_002203.mp4

Date
01/14/2022
W/O
931721
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01183
PipeID
P17304
Time
12:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9579
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_931721_TV22154_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1287
Downstream MH
H 1288
Dir. of Survey
Upstream
Length Surveyed
307.6 ft.
Total Length
307.6 ft.
Structural Index
3
Structural Quick
513K
Structural Rating
310
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
310
Pipe schematic from manhole H 1287 to H 1288
MH: H 1287MH: H 1288upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 12882.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES305.5 ft. MGO - General Observation - MAG COAT305.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start305.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start307.6 ft. MWM - Water Mark, 25 %of cross sectional area307.6 ft. AMH - Downstream Manhole, Survey Begins - H 1287307.6 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    189.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
234.9TFC
304.7SSS
304.7SAV
0MWM
2.1MGOMAG COAT
307.6AMHH 1288
2.1SSS
189.6SRV
0AMHH 1287
2.1SAV
0MWL

Properties (7)

additional_info
630074011322201
custom_field_three
AGGREGATE 7 REBAR VISIBLE/SPALLING
custom_field_two
2
customer
1
datetime
2022-01-14T00:12:01-08:00
documentation
PROPIPE
is_lateral_inspection
false