Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2022, 06:51 AM
  • H 1285_H 1284_01132022_230640.mp4

Date
01/13/2022
W/O
931721
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01183
PipeID
P17301
Time
10:51 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9579
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_931721_TV22154_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1285
Downstream MH
H 1284
Dir. of Survey
Downstream
Length Surveyed
318.5 ft.
Total Length
318.5 ft.
Structural Index
3
Structural Quick
513L
Structural Rating
316
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
316
Pipe schematic from manhole H 1285 to H 1284
MH: H 1285MH: H 1284downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 12850 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT9.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"60.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"126 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.3 ft. SRV - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES174.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"287.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.5 ft. AMH - Downstream Manhole, Survey Ends - H 1284

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

    158.3 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
12TFC
222.3TFC
287.1TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
2.1SAV
316.4SAV
318.5AMHH 1284
9.4SSS
60.5TFC
278.9TFC
158.3SRV
0AMHH 1285
230.6TF
126TF
2.1MGOMAG COAT
174.3TFC
117.4TFC
66.6TF
69.5TFC
182.3TF
0MWL
316.5SSS
0MWM

Properties (7)

additional_info
630074011322201
custom_field_three
AGGREGATE, REBAR VISIBLE/SPALLING
custom_field_two
2
customer
1
datetime
2022-01-13T22:51:31-08:00
documentation
PROPIPE
is_lateral_inspection
false