Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2022, 06:11 AM
  • 22 0246_22 0245_01102022_222309.mp4

Date
01/10/2022
W/O
931717
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16528
Time
10:11 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9763
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_931717_TV22160_JAN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0246
Downstream MH
22 0245
Dir. of Survey
Downstream
Length Surveyed
305.7 ft.
Total Length
305.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 22 0246 to 22 0245
MH: 22 0246MH: 22 0245downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02462 ft. MGO - General Observation - LINED PIPE53.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"255.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"305.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0245

Observations (9)

DistanceCodeObservation
0MWL
0MGOCONNECTION AT MH 6 O'CLOCK
0MWM
81.7TF
53.8TF
0AMH22 0246
255.5TF
305.7AMH22 0245
2MGOLINED PIPE

Properties (7)

additional_info
630098011022202
custom_field_three
RFIR NO SEVERE DEFECTS. (LINED PIPE)
custom_field_two
4
customer
1
datetime
2022-01-10T22:11:23-08:00
documentation
PROPIPE
is_lateral_inspection
false