Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 19, 2022, 06:34 AM
  • B 0634_B 0633_01182022_224920.mp4

Date
01/18/2022
W/O
931534
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00108
PipeID
P09300
Time
10:34 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9837
Sewer Name
B JOINT OUTFALL B - UNIT 8E
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_931534_TV15229_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
18 in.
Upstream MH
B 0634
Downstream MH
B 0633
Dir. of Survey
Downstream
Length Surveyed
270.6 ft.
Total Length
270.7 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
265
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
371
Pipe schematic from manhole B 0634 to B 0633
MH: B 0634MH: B 0633downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 06342 ft. MGO - General Observation - 45% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start268 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish268.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish268.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish270 ft. MGO - General Observation - ROACHES @ MH270.6 ft. AMH - Downstream Manhole, Survey Ends - B 0633270.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (3)

  • General Observation - 45% MAG COAT

    2 ft. - General Observation - 45% MAG COAT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWM
2MGO45% MAG COAT
0MWL
0AMHB 0634
268SSS
270.6AMHB 0633
2SSS
268.6DAGS
2DAGS
270.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
2SAV
268.6SAV
270MGOROACHES @ MH

Properties (7)

additional_info
630138011822201
custom_field_three
VISIBLE AGGREGATE/SPALLING
custom_field_two
2
customer
1
datetime
2022-01-18T22:34:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false