Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 19, 2022, 07:01 AM
  • B 0632_B 0631_01182022_231404.mp4

Date
01/18/2022
W/O
931534
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00108
PipeID
P09298
Time
11:01 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9837
Sewer Name
B JOINT OUTFALL B - UNIT 8E
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_931534_TV15229_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
B 0632
Downstream MH
B 0631
Dir. of Survey
Downstream
Length Surveyed
294.6 ft.
Total Length
294.6 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
290
O&M Index
2
O&M Quick
3E2K
O&M Rating
206
Overall Index
2
Overall Quick
Overall Rating
496
Pipe schematic from manhole B 0632 to B 0631
MH: B 0632MH: B 0631downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 06320 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 35% MAG COAT19.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"80 ft. MWM - Water Mark, 40 %of cross sectional area141.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS292 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish292.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish294.6 ft. AMH - Downstream Manhole, Survey Ends - B 0631294.6 ft. MGO - General Observation - ROACHES @ MH

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 35% MAG COAT

    2 ft. - General Observation - 35% MAG COAT

  • General Observation - ROACHES @ MH

    294.6 ft. - General Observation - ROACHES @ MH

Observations (17)

DistanceCodeObservation
292.7DSZ
292SAP
80MWM
294.6AMHB 0631
2SSS
2SAP
2DAGS
0MWM
19.3TFA
0MWL
294.6MGOROACHES @ MH
292SSS
0AMHB 0632
292.7DAGS
2MGO35% MAG COAT
0MGOROACHES @ MH
141.1DSZDEBRIS

Properties (7)

additional_info
630138011822201
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2022-01-18T23:01:01-08:00
documentation
PRO PIPE
is_lateral_inspection
false