Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2021, 09:06 AM
  • A 0580_A 1089_12222021_012127.mp4

Date
12/22/2021
W/O
926597
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00316
PipeID
P22155
Time
1:06 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9752
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_926597_TV21041_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
A 0580
Downstream MH
A 1089
Dir. of Survey
Downstream
Length Surveyed
48.4 ft.
Total Length
48.4 ft.
Structural Index
2
Structural Quick
4133
Structural Rating
35
O&M Index
2
O&M Quick
2A00
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
57
Pipe schematic from manhole A 0580 to A 1089
MH: A 0580MH: A 1089downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05802 ft. MGO - General Observation - STEAM IN SEWER2 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.2 ft. LL - Alignment Left, 20 %, Start12.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES26.4 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES34.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES40.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES43.9 ft. FS - Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES46 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish46 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish46.1 ft. LL - Alignment Left, 20 %, Finish48.4 ft. AMH - Downstream Manhole, Survey Ends - A 1089

Observation photos (6)

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    12.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    26.4 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    34.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    40.3 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES

    43.9 ft. - Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
2MGOSTEAM IN SEWER
0MWM
12.7CL
26.4CS
2CM
46SSS
48.4AMHA 1089
2SSS
0MWL
0AMHA 0580
46.1LL
43.9FS
2DAGS
34.3FM
5.2LL
40.3FL
46DAGS

Properties (8)

additional_info
630098122121201
custom_field_three
MULTIPLE FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2021-12-22T01:06:56-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
34989