Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 07:33 AM
  • A 0711_A 0710_12202021_233844.mp4

Date
12/20/2021
W/O
926597
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00316
PipeID
P07920
Time
11:33 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9751
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
POMONA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_926597_TV21041_DEC2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
75 in.
Upstream MH
A 0711
Downstream MH
A 0710
Dir. of Survey
Downstream
Length Surveyed
5.2 ft.
Total Length
10 ft.
Structural Index
3
Structural Quick
5232
Structural Rating
20
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole A 0711 to A 0710
MH: A 0711MH: A 0710downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 07110 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. MGO - General Observation - HEAVY STEAM IN SEWER2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.1 ft. LD - Alignment Down, 45 %5.2 ft. MSA - Survey Abandoned - VIEW OF SIPHON DOWNLEG

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0AMHA 0711
2SAP
2SSS
5SAP
0MWM
2SRC
5SSS
5.2MSAVIEW OF SIPHON DOWNLEG
5.1LD
0MWL
5SRC
0MGOHEAVY STEAM IN SEWER

Properties (8)

additional_info
630098122021201
custom_field_three
REINFORCEMENT CORRODED/AGGREGATE PROJECTING
custom_field_two
1
customer
1
datetime
2021-12-20T23:33:26-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26232