Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 08:05 PM
  • B 0011_B 0010_01262022_122345.mp4

Date
01/26/2022
W/O
926981
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08521
Time
12:05 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9585
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_926981_TV08132_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
33 in.
Upstream MH
B 0010
Downstream MH
B 0011
Dir. of Survey
Upstream
Length Surveyed
344.6 ft.
Total Length
344.6 ft.
Structural Index
3
Structural Quick
5C3M
Structural Rating
297
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
297
Pipe schematic from manhole B 0010 to B 0011
MH: B 0010MH: B 0011upstream0 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN REBAR0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - CAMERA BLKD BY SURFACE REINFORCEMENT0 ft. MGO - General Observation - REINFORCEMENT OBSTRUCTING FLOW88.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR342.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start342.6 ft. MGO - General Observation - MAG COATING THROUGHOUT344.6 ft. MWM - Water Mark, 40 %of cross sectional area344.6 ft. MWL - Water Level, 20 %of cross sectional area344.6 ft. MGO - Reversal Inspection344.6 ft. AMH - Downstream Manhole, Survey Begins - B 0010

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - REINFORCEMENT OBSTRUCTING FLOW

    344.6 ft. - General Observation - REINFORCEMENT OBSTRUCTING FLOW

Observations (11)

DistanceCodeObservation
0MWM
256.5SRCBROKEN REBAR
344.6SRCBROKEN REBAR
344.6SAV
0MWL
2SAV
2MGOMAG COATING THROUGHOUT
0MGO
0AMHB 0010
344.6MSACAMERA BLKD BY SURFACE REINFORCEMENT
344.6MGOREINFORCEMENT OBSTRUCTING FLOW

Properties (8)

additional_info
630098012622051
custom_field_three
REINFORCEMENT CORRODED
custom_field_two
5
customer
1
datetime
2022-01-26T12:05:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36930