Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 06:44 PM
  • B 0011_B 0010_01262022_111941.mp4

Date
01/26/2022
W/O
926981
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08521
Time
10:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9585
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_926981_TV08132_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
33 in.
Upstream MH
B 0011
Downstream MH
B 0010
Dir. of Survey
Downstream
Length Surveyed
167 ft.
Total Length
167 ft.
Structural Index
4
Structural Quick
5F3F
Structural Rating
264
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
264
Pipe schematic from manhole B 0011 to B 0010
MH: B 0011MH: B 0010downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 00112.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COATING THROUGHOUT2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR26.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish152.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"167 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BROKEN REBAR167 ft. MGO - General Observation - REINFORCEMENT OBSTRUCTING FLOW167 ft. MSA - Survey Abandoned - CAMERA BLKD BY REINFORCEMENT167 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR

    26.2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR

  • General Observation - REINFORCEMENT OBSTRUCTING FLOW

    167 ft. - General Observation - REINFORCEMENT OBSTRUCTING FLOW

Observations (13)

DistanceCodeObservation
0MWL
2.1SAP
26.2SRCBROKEN REBAR
167SRCBROKEN REBAR
26.2SRV
0MWM
167MGOREINFORCEMENT OBSTRUCTING FLOW
167MSACAMERA BLKD BY REINFORCEMENT
167SAP
0AMHB 0011
2.1MGOMAG COATING THROUGHOUT
2.1SRV
152.8TFA

Properties (8)

additional_info
630098012622051
custom_field_three
BROKEN REBAR
custom_field_two
1
customer
1
datetime
2022-01-26T10:44:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36930