Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2022, 10:04 PM
  • B 0008_B 0007_01272022_143300.mp4

Date
01/27/2022
W/O
926981
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08518
Time
2:04 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9586
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_926981_TV08132_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
33 in.
Upstream MH
B 0008
Downstream MH
B 0007
Dir. of Survey
Downstream
Length Surveyed
1053 ft.
Total Length
1053 ft.
Structural Index
3
Structural Quick
5i3i
Structural Rating
2100
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
2100
Pipe schematic from manhole B 0008 to B 0007
MH: B 0008MH: B 0007downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 00080 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start226.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"1053 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1053 ft. AMH - Downstream Manhole, Survey Ends - B 0007 ZOOMED IN1053 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1053 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BROKEN REBAR

Observation photos (3)

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BROKEN REBAR

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
1053SAP
0AMHB 0008
1053AMHB 0007 ZOOMED IN
0MWM
0MWL
1053SSS
226.5TFA
2SRCBROKEN REBAR
1053SRCBROKEN REBAR
2SAP
2MGOMAG COATING THROUGHOUT
2SSS

Properties (8)

additional_info
630098012722061
custom_field_three
BROKEN REBAR/SPALLING
custom_field_two
1
customer
1
datetime
2022-01-27T14:04:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36930