Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2022, 04:36 PM
  • B 0006_B 0005_01282022_085558.mp4

Date
01/28/2022
W/O
926981
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00072
PipeID
P08516
Time
8:36 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9587
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_926981_TV08132_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Width
33 in.
Upstream MH
B 0006
Downstream MH
B 0005
Dir. of Survey
Downstream
Length Surveyed
622.8 ft.
Total Length
622.8 ft.
Structural Index
4
Structural Quick
5X3q
Structural Rating
1374
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
1376
Pipe schematic from manhole B 0006 to B 0005
MH: B 0006MH: B 0005downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 00060 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start88.2 ft. OBP - Obstacles External Pipe or Cable, 10 %of cross sectional area, from 10 to 02 o'clock197 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR444 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: NO - BROKEN REBAR622.8 ft. AMH - Downstream Manhole, Survey Ends - B 0005 ZOOMED IN622.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish622.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish622.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK622.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Obstacles External Pipe or Cable, 10 %of cross sectional area, from 10 to 02 o'clock

    88.2 ft. - Obstacles External Pipe or Cable, 10 %of cross sectional area, from 10 to 02 o'clock

Observations (15)

DistanceCodeObservation
2MGOMAG COATING THROUGHOUT
444SRCBROKEN REBAR
2SRV
197SRCBROKEN REBAR
622.8AMHB 0005 ZOOMED IN
2SAV
0AMHB 0006
88.2OBP
622.8SAV
0MWL
622.8SAV
2SAV
0MWM
622.8MGOCONNECTION AT MH 3 O'CLOCK
622.8SRV

Properties (8)

additional_info
630098012822061
custom_field_three
BROKEN REBAR/SPALLING
custom_field_two
1
customer
1
datetime
2022-01-28T08:36:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
36930