Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2022, 07:24 AM
  • D 0211_D 0123_01122022_234918.mp4

Date
01/12/2022
W/O
926598
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10033
Time
11:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9577
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_926598_TV05172_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Square
Height
30 in.
Width
27 in.
Upstream MH
D 0211
Downstream MH
D 0123
Dir. of Survey
Downstream
Length Surveyed
313.1 ft.
Total Length
313.1 ft.
Structural Index
3
Structural Quick
5L3K
Structural Rating
625
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
625
Pipe schematic from manhole D 0211 to D 0123
MH: D 0211MH: D 0123downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 02110 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start216.3 ft. SRC - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES311.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish313.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK313.1 ft. AMH - Downstream Manhole, Survey Ends - D 0123

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES

    216.3 ft. - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0MWM
2.1SAP
2.1SRV
311.4SAP
313.1MGOCONNECTION AT THE MH 9 OC'LOCK
0AMHD 0211
2.1SSS
311.4SSS
216.3SRC
311.4SRV
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
313.1AMHD 0123

Properties (7)

additional_info
630074011222201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT BROKEN/SPALLIN
custom_field_two
1
customer
1
datetime
2022-01-12T23:24:12-08:00
documentation
PROPIPE
is_lateral_inspection
false