Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2021, 05:31 AM
  • D 0102_D 0101_12282021_214425.mp4

Date
12/28/2021
W/O
926598
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10008
Time
9:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9574
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_926598_TV05172_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
57 in.
Upstream MH
D 0102
Downstream MH
D 0101
Dir. of Survey
Downstream
Length Surveyed
498.2 ft.
Total Length
498.2 ft.
Structural Index
3
Structural Quick
5S3S
Structural Rating
980
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
980
Pipe schematic from manhole D 0102 to D 0101
MH: D 0102MH: D 0101downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01022.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start494.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish494.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish494.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish498.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK498.2 ft. AMH - Downstream Manhole, Survey Ends - D 0101

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
2.3SRV
494.6SAP
2.3SSS
498.2MGOCONNECTION AT THE MH 9 OC'LOCK
494.6SRV
0MWM
0AMHD 0102
2.3SAP
498.2AMHD 0101
494.6SSS

Properties (7)

additional_info
630074122821201
custom_field_three
AGGREGATE PROJECTING/SPALLING REINFORCEMENT VISIBL
custom_field_two
2
customer
1
datetime
2021-12-28T21:31:17-08:00
documentation
PROPIPE
is_lateral_inspection
false