Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2022, 12:14 PM
  • 18 0492_18 0491_272022_041505.mp4

Date
02/07/2022
W/O
0931911
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14346
Time
4:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3005
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20220203MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0491
Downstream MH
18 0492
Dir. of Survey
Upstream
Length Surveyed
142.3 ft.
Total Length
142.3 ft.
Structural Index
3
Structural Quick
5139
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
50
Pipe schematic from manhole 18 0491 to 18 0492
MH: 18 0491MH: 18 0492upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:05(INSPECTION COMPLETED REVERSE INSPECTION)0.7 ft. RPP - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR0.7 ft. RPP - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR0.7 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET- MISALIGNED1.7 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL8.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL15.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H35 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H40.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL47.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H50.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H60.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL66.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H68.6 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL70.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H71.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H71.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL72.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, - H74.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H76.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL83.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H87.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H93.6 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H95.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL95.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL125.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - SLIGHT128.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT142.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active142.3 ft. AMH - Downstream Manhole, Survey Begins - 4:25AM142.3 ft. MWL - Water Level, 10 %of cross sectional area142.3 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (5)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    13.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    67.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    71.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR

    141.6 ft. - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR

  • Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR

    141.6 ft. - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - INCASED REPAIR

Observations (31)

DistanceCodeObservation
69.5FLH
0AMH4:25AM
46.4FLSL
140.6FCSL
0MWL
13.8FLSLIGHT
101.6FCSL
82.1FLSL
134.2FCSL
94.7FLH
0.1MGOConn. @ Mh, 3 O' Clock. Active
107.3FLH
65.9FCSL
142.3AMH4:05(INSPECTION COMPLETED REVERSE INSPECTION)
75.8FCH
73.7FCSL
48.7FCH
71.2FLH
71.7FCH
58.9FLH
141.6RPPINCASED REPAIR
126.8FLH
0MWM
141.6RPPINCASED REPAIR
91.7FLH
141.6BOFFSET- MISALIGNED
54.4FLH
71.2FLSL
67.6FLH
16.5FLSLIGHT
46.4FCSL

Properties (7)

additional_info
REVERSE INSPECTION
custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER-BROKEN PIPE
custom_field_two
2
customer
LACSD
datetime
2022-02-07T04:14:50-08:00
documentation
MARTIN,REVELES,CASTILLO
is_lateral_inspection
false