Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2022, 11:21 AM
  • 18 0492_18 0491_272022_032504.mp4

Date
02/07/2022
W/O
0931911
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14346
Time
3:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3005
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20220203MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0492
Downstream MH
18 0491
Dir. of Survey
Downstream
Length Surveyed
32.9 ft.
Total Length
32.9 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 18 0492 to 18 0491
MH: 18 0492MH: 18 0491downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:25AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT3.5 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL5.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SL8.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SL8.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL13.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL31.9 ft. RPP - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED31.9 ft. RPP - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED31.9 ft. RPP - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED32.3 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET32.9 ft. MSA - Survey Abandoned - INCASED MISSING PIPE AREA(WILL COMPLERTE REVERESE INSPECTION

Observation photos (6)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SL

    5.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SL

  • Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

    31.9 ft. - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

  • Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

    31.9 ft. - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

  • Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

    31.9 ft. - Repair Patch, from 02 to 10 o'clock, within 8 inches of joint: YES - MISSING PIPE INCASED

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET

    32.3 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES - OFFSET

  • Survey Abandoned - INCASED MISSING PIPE AREA(WILL COMPLERTE REVERESE INSPECTION

    32.9 ft. - Survey Abandoned - INCASED MISSING PIPE AREA(WILL COMPLERTE REVERESE INSPECTION

Observations (15)

DistanceCodeObservation
13.4FCSL
32.9MSAINCASED MISSING PIPE AREA(WILL COMPLERTE REVERESE INSPECTION
31.9RPPMISSING PIPE INCASED
0MWL
0AMH3:25AM
31.9RPPMISSING PIPE INCASED
31.9RPPMISSING PIPE INCASED
8.3FMSL
8.3FCSL
32.3BOFFSET
3.5FCSL
0MGOConn. @ Mh, 3 O' Clock. OPEN
5.2FMSL
0MWM
2FCSLIGHT

Properties (6)

custom_field_three
BROKEN PIPE-LARGE REPAIR
custom_field_two
2
customer
LACSD
datetime
2022-02-07T03:21:23-08:00
documentation
MARTIN,REVELES,CASTILLO
is_lateral_inspection