Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2022, 08:32 AM
  • 18 0495_18 0494A_272022_010924.mp4

Date
02/07/2022
W/O
0931911
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P27096
Time
12:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3004
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20220203MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0495
Downstream MH
18 0494A
Dir. of Survey
Downstream
Length Surveyed
418.8 ft.
Total Length
418.8 ft.
Structural Index
3
Structural Quick
533C
Structural Rating
118
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
120
Pipe schematic from manhole 18 0495 to 18 0494A
MH: 18 0495MH: 18 0494Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active18.5 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - SLIGHT21.4 ft. RPP - Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - APPEARS CONCRETE INCASED23.7 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL46.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE54.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL56.8 ft. RFJ - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YESR - 1%62.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H73.1 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - MULTIPLE FRACTURES POSSIBLE REPAIR73.2 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE REPAIRE CONCRETE INCASED77.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H95 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL95 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL99.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H99.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL104.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H109.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H112.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H119.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H130.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H140.2 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%150.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL150.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL153.1 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL155.1 ft. MMC - Material Change, Concrete pipe (non-reinfored) - POSSIBLE INCASEMENT159.6 ft. MGO - General Observation - POSSIBLE METAL PIPE160.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H160.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL160.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL162 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL163.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL163.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL163.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - SL168.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H174.3 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES - OFFSET LONG SLIGHT FRACTURE176.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H176.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H181.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL184.5 ft. BSV - Broken Soil Visible, at 12 o'clock, within 8 inches of joint: YES - 1" WIDE X 2" LONG196.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL201.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL208.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL231.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL245.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES, - SL272.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL279.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active283.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL296.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL332.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H337.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL342.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H347.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H352 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H373.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SSL375.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL375.7 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start - H380.8 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Finish - H383 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - H385.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL389.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H396.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H418 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN418 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT418 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish418.8 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (15)

  • Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - APPEARS CONCRETE INCASED

    21.4 ft. - Repair Patch, from 10 to 02 o'clock, within 8 inches of joint: YES - APPEARS CONCRETE INCASED

  • Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - MULTIPLE FRACTURES POSSIBLE REPAIR

    73.1 ft. - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - MULTIPLE FRACTURES POSSIBLE REPAIR

  • Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE REPAIRE CONCRETE INCASED

    73.2 ft. - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES - POSSIBLE REPAIRE CONCRETE INCASED

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    95 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    150.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Material Change, Concrete pipe (non-reinfored) - POSSIBLE INCASEMENT

    155.1 ft. - Material Change, Concrete pipe (non-reinfored) - POSSIBLE INCASEMENT

  • General Observation - POSSIBLE METAL PIPE

    159.6 ft. - General Observation - POSSIBLE METAL PIPE

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H

    160.6 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    160.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

    160.6 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

  • Broken, at 12 o'clock, within 8 inches of joint: YES - OFFSET LONG SLIGHT FRACTURE

    174.3 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES - OFFSET LONG SLIGHT FRACTURE

  • Broken Soil Visible, at 12 o'clock, within 8 inches of joint: YES - 1" WIDE X 2" LONG

    184.5 ft. - Broken Soil Visible, at 12 o'clock, within 8 inches of joint: YES - 1" WIDE X 2" LONG

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    231.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    283.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SSL

    373.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SSL

Observations (69)

DistanceCodeObservation
176.9FCH
231.2FLSL
380.8FLH
159.6MGOPOSSIBLE METAL PIPE
46.8FCHAIRLINE
196.5FCSL
418MGOConn. @ Mh, 9 O' Clock. OPEN
104.7FLH
23.7FCSL
162FCSL
163.8FLSL
99.9FCH
153.1FCSL
95FCSL
163.8FLSL
332.4FCH
77.3FLH
62.5FLH
168.5FCH
201.7FCSL
160.6FLH
385.9FCSL
418FLSLIGHT
130.3FLH
174.3BOFFSET LONG SLIGHT FRACTURE
279.1TFAActive
181.1FCSL
208.8FLSL
140.2RFJ2%
160.6FLSL
375.7FCSL
56.8RFJ1%
0MWL
342.6FLH
95FLSL
396.1FCH
176.2FCH
296.3FLSL
337.6FCSL
155.1MMCPOSSIBLE INCASEMENT
0MWM
160.6FLSL
347.6FCH
0MGOConn. @ Mh, 3 O' Clock. Active
18.5FCSLIGHT
245.4FCSL
373.9FLSSL
418.8AMH1:50AM
73.2BPOSSIBLE REPAIRE CONCRETE INCASED
389.1FCH
73.1BMULTIPLE FRACTURES POSSIBLE REPAIR
163.8FLSL
272.9FLSL
184.5BSV1" WIDE X 2" LONG
352FLH
0AMH12:50AM
383FLH
109.5FLH
283.9FLSL
21.4RPPAPPEARS CONCRETE INCASED
54.9FCSL
150.4FCSL
99.9FLSL
112.5FLH
418FL
375.7FLH
0MGOConn. @ Mh, 9 O' Clock. Active
119.4FLH
150.4FLSL

Properties (6)

custom_field_three
POSIBLE BROKEN PIPE SPOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2022-02-07T00:32:46-08:00
documentation
MARTIN,REVELES,CASTILLO
is_lateral_inspection
false