Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 09:08 AM
  • 18 0583_18 0582_282022_011636.mp4

Date
02/08/2022
W/O
0937404
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14708
Time
1:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3006
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
20220208MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0582
Downstream MH
18 0583
Dir. of Survey
Upstream
Length Surveyed
6.5 ft.
Total Length
6.5 ft.
Structural Index
4
Structural Quick
5241
Structural Rating
16
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
21
Pipe schematic from manhole 18 0582 to 18 0583
MH: 18 0582MH: 18 0583upstream0 ft. MSA - Survey Abandoned - VEIW UPLG DOWNSTREAM SIPHON0.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - BLISTERING PEELING CONCRETE0.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - LONG CIRCUM REBAR0.5 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE0.5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG4.5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG4.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - BLISTERING PEELING CONCRETE4.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR6.5 ft. MWM - Water Mark, 80 %of cross sectional area6.5 ft. MWL - Water Level, 80 %of cross sectional area6.5 ft. AMH - Downstream Manhole, Survey Begins - 1:20AM

Observation photos (5)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

    6 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

  • Survey Abandoned - VEIW UPLG DOWNSTREAM SIPHON

    6.5 ft. - Survey Abandoned - VEIW UPLG DOWNSTREAM SIPHON

Observations (11)

DistanceCodeObservation
6SSSBLISTERING PEELING CONCRETE
0MWM
0MWL
6SRCLONG CIRCUM REBAR
2SAMSEVERE AGG
6SMWPOSSIBLE SOIL VISIBLE
2SSSBLISTERING PEELING CONCRETE
0AMH1:20AM
6.5MSAVEIW UPLG DOWNSTREAM SIPHON
6SAMSEVERE AGG
2SRCLONG CIRCUM REBAR

Properties (7)

additional_info
UPLEG DOWNSTREAM SIPHON
custom_field_three
SOIL VISIBLE SLIGHT VOID
custom_field_two
1
customer
LACSD
datetime
2022-02-08T01:08:09-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false