- Date
- 12/16/2021
- W/O
- 926452
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00821
- PipeID
- P25920
- Time
- 11:59 PM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9649
- Sewer Name
- 22 PUDDINGSTONE TRUNK, SECTS 1&2
- City
- SAN DIMAS
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- RFIR_WO_926452_TV22097_DEC2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 22 0740
- Downstream MH
- 22 0739A
- Dir. of Survey
- Downstream
- Length Surveyed
- 134.5 ft.
- Total Length
- 134.5 ft.
- Structural Index
- 2
- Structural Quick
- 3C2D
- Structural Rating
- 118
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 118
Pipe schematic from manhole 22 0740 to 22 0739A Observation photos (3)

2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

20.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

32.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start