Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2021, 06:34 AM
  • A 0879_A 0878_12022021_224835.mp4

Date
12/02/2021
W/O
921697
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00318
PipeID
P07973
Time
10:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9553
Sewer Name
A JOA-1A FLORENCE AVENUE INTERCEPTOR
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_921697_TV18067_NOV2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
63 in.
Upstream MH
A 0878
Downstream MH
A 0879
Dir. of Survey
Upstream
Length Surveyed
571.9 ft.
Total Length
571.9 ft.
Structural Index
3
Structural Quick
3V2V
Structural Rating
570
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
570
Pipe schematic from manhole A 0878 to A 0879
MH: A 0878MH: A 0879upstream0 ft. AMH - Upstream Manhole, Survey Ends - A 08790.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish568.1 ft. MGO - General Observation - MAG COAT569.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start569.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start571.9 ft. AMH - Downstream Manhole, Survey Begins - A 0878571.9 ft. MWL - Water Level, 20 %of cross sectional area571.9 ft. MWM - Water Mark, 20 %of cross sectional area

Observations (9)

DistanceCodeObservation
0AMHA 0878
2SSS
0MWL
571SSS
3.8MGOMAG COAT
0MWM
571.9AMHA 0879
2SAV
571SAV

Properties (8)

additional_info
630074120221201
custom_field_three
SPALLING/AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-12-02T22:34:52-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31303