Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 11:58 AM
  • G 0086_G 0016_212022_052304.mp4

Date
02/01/2022
W/O
0937398
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02174
Time
3:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2097
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20220131MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0086
Downstream MH
G 0016
Dir. of Survey
Downstream
Length Surveyed
8 ft.
Total Length
8 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole G 0086 to G 0016
MH: G 0086MH: G 0016downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active LARGE IN COMING0 ft. AMH - Upstream Manhole, Survey Begins - 5:25AM0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG REBAR BROKEN MISSING2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG8 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (3)

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG REBAR BROKEN MISSING

    2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG REBAR BROKEN MISSING

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (8)

DistanceCodeObservation
2SRCLONG REBAR BROKEN MISSING
0MWM
0MGOConn. @ Mh, 3 O' Clock. Active LARGE IN COMING
0AMH5:25AM
8AMH5:30AM
2SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG
0MWL

Properties (6)

custom_field_three
LONG REBAR BROKEN MISSING
custom_field_two
2
customer
LACSD
datetime
2022-02-01T03:58:26-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false