Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 11:58 AM
  • G 0114_G 0113_212022_041632.mp4

Date
02/01/2022
W/O
0937398
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01441
Time
3:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2098
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20220131MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0114
Downstream MH
G 0113
Dir. of Survey
Downstream
Length Surveyed
288.8 ft.
Total Length
288.8 ft.
Structural Index
5
Structural Quick
5941
Structural Rating
51
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
55
Pipe schematic from manhole G 0114 to G 0113
MH: G 0114MH: G 0113downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM2 ft. MGO - General Observation - TILES 99% MISSING2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 90%2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORROSON BEYOUND REBAR3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG33 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR57.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW84.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW123.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING173.3 ft. SMW - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE178.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING257.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING IN FLOW288.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG288.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active288.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR BROKEN MISSING288.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE288.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active288.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORROSON BEYOUND REBAR288.8 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (13)

  • General Observation - TILES 99% MISSING

    2 ft. - General Observation - TILES 99% MISSING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 90%

    2 ft. - General Observation - MAG COAT 90%

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORROSON BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORROSON BEYOUND REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    33 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW

    57.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW

    84.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - REBAR HANGING IN FLOW

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING

    123.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING

  • Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

    173.3 ft. - Surface Missing Wall, from 01 to 02 o'clock, within 8 inches of joint: NO - POSSIBLE SOIL VISIBLE

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING

    178.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING IN FLOW

    257.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING IN FLOW

Observations (23)

DistanceCodeObservation
257.6SRCHANGING IN FLOW
0MWM
2MGOTILES 99% MISSING
0MWL
288.1SAMSEVERE AGG
173.3SMWPOSSIBLE SOIL VISIBLE
288.1MGOConn. @ Mh, 3 O' Clock. Active
2SSSBLISTERING PEELING CONCRETE
84.8SRCREBAR HANGING IN FLOW
123.8SRCHANGING
2MGOMAG COAT 90%
178.4SRCHANGING
288.1SRCLONG CIRCUM REBAR BROKEN MISSING
288.1SSSBLISTERING PEELING CONCRETE
0AMH4:15AM
33SRCBROKEN MISSING REBAR
2SRCBROKEN MISSING REBAR
288.1MGOConn. @ Mh, 9 O' Clock. Active
288.1SRCCORROSON BEYOUND REBAR
57.2SRCREBAR HANGING IN FLOW
2SRCCORROSON BEYOUND REBAR
3SAMSEVERE AGG
288.8AMH4:50AM

Properties (6)

custom_field_three
LONG CIRCUM REBAR MISSING -POSSIBLE SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2022-02-01T03:58:14-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false