Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2022, 08:14 AM
  • G 0118_G 0117_1312022_013113.mp4

Date
01/31/2022
W/O
0937398
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01445
Time
12:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2096
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20220131MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0118
Downstream MH
G 0117
Dir. of Survey
Downstream
Length Surveyed
355.1 ft.
Total Length
355.1 ft.
Structural Index
5
Structural Quick
5721
Structural Rating
37
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
42
Pipe schematic from manhole G 0118 to G 0117
MH: G 0118MH: G 0117downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 80 %of cross sectional area2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING2 ft. MGO - General Observation - TILES 99% MISSING8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUMN REBAR CORRODED & BROKEN18.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING CIRCUM REBAR44.6 ft. MGO - General Observation - 30% MISSING TILES START67.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR94.9 ft. MGO - General Observation - 80% MISSING TILES START150.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR243.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR346.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM RE AR CORRODED & MISSING355.1 ft. MGO - General Observation - 80% MISSING TILES FINISH355.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active355.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE355.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED & MISSING355.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN CORRODED REBAR MISSING355.1 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (11)

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED & MISSING

  • General Observation - TILES 99% MISSING

    2 ft. - General Observation - TILES 99% MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUMN REBAR CORRODED & BROKEN

    8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUMN REBAR CORRODED & BROKEN

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING CIRCUM REBAR

    18.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING CIRCUM REBAR

  • General Observation - 30% MISSING TILES START

    44.6 ft. - General Observation - 30% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    67.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 80% MISSING TILES START

    94.9 ft. - General Observation - 80% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    150.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    243.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM RE AR CORRODED & MISSING

    346.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM RE AR CORRODED & MISSING

Observations (20)

DistanceCodeObservation
355.1MGO80% MISSING TILES FINISH
355.1MGOConn. @ Mh, 9 O' Clock. Active
355.1SSSBLISTERING PEELING CONCRETE
18.9SRCMISSING CIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
2SRCLONG CIRCUM REBAR CORRODED & MISSING
94.9MGO80% MISSING TILES START
355.1SRCLONG CIRCUM REBAR CORRODED & MISSING
0AMH12:55AM
8SRCCIRCUMN REBAR CORRODED & BROKEN
355.1SRCBROKEN CORRODED REBAR MISSING
0MWM
355.1AMH1:50AM
346.5SRCLONG CIRCUM RE AR CORRODED & MISSING
0MWL
150.7SRCLONG & CIRCUM REBAR
243.6SRCCIRCUM REBAR
44.6MGO30% MISSING TILES START
2MGOTILES 99% MISSING
67.5SRCCIRCUM REBAR

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED MISSING
custom_field_two
1
customer
LACSD
datetime
2022-01-31T00:14:56-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false