Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 12:39 PM
  • 08 0001_08 0000_1262022_050147.mp4

Date
01/26/2022
W/O
0936276
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00561
PipeID
P21471
Time
4:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2093
Sewer Name
08 MAIN STREET P.P. INFLUENT SEWER
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20220126MDM_MAIN_STREET_P_P_INFLUENT_SEWER
Material
CIP
Shape
Circular
Height
30 in.
Upstream MH
08 0001
Downstream MH
08 0000
Dir. of Survey
Downstream
Length Surveyed
3 ft.
Total Length
3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 08 0001 to 08 0000
MH: 08 0001MH: 08 0000downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active DROP ACTIVE IN MYH STACK POURING DOWN0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWL - Water Level, 95 %of cross sectional area0 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. SCP - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 50% OR MORE MISSING PIPE3 ft. MSA - Survey Abandoned - 95% FLOW

Observation photos (2)

  • Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 50% OR MORE MISSING PIPE

    2 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 50% OR MORE MISSING PIPE

  • Survey Abandoned - 95% FLOW

    3 ft. - Survey Abandoned - 95% FLOW

Observations (6)

DistanceCodeObservation
3MSA95% FLOW
0MGOConn. @ Mh, 9 O' Clock. Active DROP ACTIVE IN MYH STACK POURING DOWN
0AMH5:05AM
2SCP50% OR MORE MISSING PIPE
0MWL
0MWM

Properties (4)

customer
LACSD
datetime
2022-01-26T04:39:47-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false