Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2022, 08:18 PM
Date
01/31/2022
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00254
PipeID
P04103
Time
12:18 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
I0389
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Maintenance Related
Project
20220131DF_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
02 1758
Downstream MH
02 1757A
Dir. of Survey
Downstream
Length Surveyed
164.6 ft.
Total Length
164.6 ft.
Structural Index
3
Structural Quick
513E
Structural Rating
101
O&M Index
2
O&M Quick
2E12
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
167
Pipe schematic from manhole 02 1758 to 02 1757A
MH: 02 1758MH: 02 1757Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 12:21 PM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.9 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES53.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"91.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 5% ROOTS102 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4" - 10% ROOTS-LATERAL110 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 5% ROOTS162.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish162.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish163 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE164.6 ft. AMH - Downstream Manhole, Survey Ends - 12:43 PM

Observations (15)

DistanceCodeObservation
102TFA10% ROOTS-LATERAL
0MWM
4.9B
91.4RFJ5% ROOTS
162.1CM
0MWL
0MGOCONN @ MH 3 O'CLOCK/OPEN
110RFJ5% ROOTS
0AMH12:21 PM
163MGOCONN @ MH 3 O'CLOCK/ACTIVE
2DAGS
162.1DAGS
53.8TFA
2CM
164.6AMH12:43 PM

Properties (6)

custom_field_three
FRACTURES
custom_field_two
2
customer
LACSD
datetime
2022-01-31T12:18:26-08:00
documentation
FRANKLIN, BRAR, RAMIREZ, RUVALCABA
is_lateral_inspection
false