Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2021, 08:32 AM
  • 02 1755_02 1754_12172021_004642.mp4

Date
12/17/2021
W/O
926959
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00254
PipeID
P04098
Time
12:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9640
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Routine Assessment
Project
RFIR_WO_926959_TV02243_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
02 1755
Downstream MH
02 1754
Dir. of Survey
Downstream
Length Surveyed
293.2 ft.
Total Length
293.2 ft.
Structural Index
3
Structural Quick
3G21
Structural Rating
119
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
235
Pipe schematic from manhole 02 1755 to 02 1754
MH: 02 1755MH: 02 1754downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 17550 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start74.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"92.9 ft. CS - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES97.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start204.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish291.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ABANDONED293.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1754293.2 ft. MGO - General Observation - ROACHES @ MH

Observation photos (5)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    92.9 ft. - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    97.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    293.2 ft. - General Observation - ROACHES @ MH

Observations (16)

DistanceCodeObservation
2DAGS
293MGOCONN @ MH 9 O'CLOCK/ABANDONED
204.4TFC
291.1DAGS
0AMH02 1755
92.9CS
74.8TF
0MWM
97.4CM
291.1CM
0MGOROACHES @ MH
0MWL
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
293.2AMH02 1754
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
293.2MGOROACHES @ MH

Properties (7)

additional_info
630138121621202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-12-17T00:32:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false