Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2021, 11:00 AM
  • 01 0535_01 0534_12172021_031305.mp4

Date
12/17/2021
W/O
926527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01022
Time
3:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9641
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926527_TV01239_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0535
Downstream MH
01 0534
Dir. of Survey
Downstream
Length Surveyed
330.9 ft.
Total Length
330.9 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
4121
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0535 to 01 0534
MH: 01 0535MH: 01 0534downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 05350 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"82 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"105.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"156.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"186.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"261.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"303.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"303.4 ft. RFC - Roots Fine Connection, from 11 to 12 o'clock328.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish328.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.9 ft. MGO - General Observation - COCKROACHES IN MH330.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0534

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 11 to 12 o'clock

    303.4 ft. - Roots Fine Connection, from 11 to 12 o'clock

  • General Observation - COCKROACHES IN MH

    330.9 ft. - General Observation - COCKROACHES IN MH

Observations (22)

DistanceCodeObservation
34.9TFC
2.8FM
303.4TFA
186.6TFC
210.1TFA
105.9TFC
0AMH01 0535
2DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
132.6TFC
328.9DAGS
303.4RFC
328.9FM
82TFC
0MGOCOCKROACHES IN MH
261.1TFA
156.5TFA
330.9MGOCOCKROACHES IN MH
330.9AMH01 0534
64.4TFA
0MWL
0MWM

Properties (7)

additional_info
630138121621203
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-12-17T03:00:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false