Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 07:43 AM
  • 01 0526_01 0525_12212021_000101.mp4

Date
12/20/2021
W/O
926527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01011
Time
11:43 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9644
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926527_TV01239_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0526
Downstream MH
01 0525
Dir. of Survey
Downstream
Length Surveyed
290.4 ft.
Total Length
290.4 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0526 to 01 0525
MH: 01 0526MH: 01 0525downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"36 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"84.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"132.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"135 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"183 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"234.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"284.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"287.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"288.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish290.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0525, ABANDONED MH

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - 01 0525, ABANDONED MH

    290.4 ft. - Downstream Manhole, Survey Ends - 01 0525, ABANDONED MH

Observations (20)

DistanceCodeObservation
0MWM
4.4FM
132.1TFC
84.8TFC
2DAGS
290.4AMH01 0525, ABANDONED MH
236.7TF
135TFC
185.8TFC
287.6TFC
234.6TFC
288.4FM
0MWL
86.7TFC
0AMH01 0526
36TFC
183TFC
33.8TFC
284.9TF
288.4DAGS

Properties (7)

additional_info
630138122021201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2021-12-20T23:43:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false