Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 09:24 AM
  • 01 0520_01 0519_12212021_014229.mp4

Date
12/21/2021
W/O
926527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01004
Time
1:24 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9644
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926527_TV01239_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0520
Downstream MH
01 0519
Dir. of Survey
Downstream
Length Surveyed
306.6 ft.
Total Length
306.6 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 01 0520 to 01 0519
MH: 01 0520MH: 01 0519downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05200 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - COCKROACHES IN MH3.4 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES5.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"8 ft. H - Hole, from 09 to 12 o'clock, within 8 inches of joint: YES9.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"40.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"79.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"82.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"170.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"209.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"256.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish304.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish306.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0519306.6 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    2 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    3.4 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Hole, from 09 to 12 o'clock, within 8 inches of joint: YES

    8 ft. - Hole, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    306.6 ft. - General Observation - COCKROACHES IN MH

Observations (29)

DistanceCodeObservation
0MWM
14TFA
82.7TBA
147.1TFA
286.3TFA
2DAGS
306.6AMH01 0519
49.2TFA
304.4CM
106.4TFC
132.6TFC
179.6TFA
9.5CM
79.3TFC
304.4DAGS
256.7TF
40.8TFC
111.9TFA
209.8TFC
5.3TFA
211.9TFD
2MGOCOCKROACHES IN MH
0AMH01 0520
253.7TFA
8H
306.6MGOCOCKROACHES IN MH
170.8TFC
0MWL
3.4CM

Properties (7)

additional_info
630138122021201
custom_field_three
HOLE/CRACKS
custom_field_two
2
customer
1
datetime
2021-12-21T01:24:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false