Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2021, 09:42 AM
  • 01 0519_01 0518_12212021_020133.mp4

Date
12/21/2021
W/O
926527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01003
Time
1:42 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9644
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926527_TV01239_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0519
Downstream MH
01 0518
Dir. of Survey
Downstream
Length Surveyed
302.7 ft.
Total Length
302.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 01 0519 to 01 0518
MH: 01 0519MH: 01 0518downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05190 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"12.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.2 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES45 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"45 ft. RMC - Roots Medium Connection, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YES51.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS75.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start148.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"210.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"301.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish301.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0518302.7 ft. MGO - General Observation - COCKROACHES IN MH302.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    37.2 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YES

    45 ft. - Roots Medium Connection, from 08 to 12 o'clock, 15 %, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    125.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    302.7 ft. - General Observation - COCKROACHES IN MH

Observations (27)

DistanceCodeObservation
301.1CM
2DAGS
298.4TFA
166.5TFA
12.3TFA
0MWM
302.7AMH01 0518
51.3DSZDEBRIS
75.3TFC
302.7MGOCOCKROACHES IN MH
125.8CM
0MWL
210.7TFC
301.1DSZ
256TFA
45TFA
0AMH01 0519
112TFA
205.2TFC
45RMC
148.3TFA
302.7MGOCONNECTION AT MH 3 O'CLOCK
301.1DAGS
9.4TFC
37.2CS
209.8TBA
0MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138122021201
custom_field_three
MULTIPLE CRACKS/DEBRIS
custom_field_two
2
customer
1
datetime
2021-12-21T01:42:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false