Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2021, 04:51 PM
  • 29 0743_29 0742_11122021_092927.mp4

Date
11/12/2021
W/O
921553
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00527
PipeID
P24249
Time
8:51 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9280
Sewer Name
29 ALAMITOS PUMPING PLANT TRUNK
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_921553_TV29079_NOV2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0742
Downstream MH
29 0743
Dir. of Survey
Upstream
Length Surveyed
354.9 ft.
Total Length
354.9 ft.
Structural Index
3
Structural Quick
4M3N
Structural Rating
521
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
653
Pipe schematic from manhole 29 0742 to 29 0743
MH: 29 0742MH: 29 0743upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 07430 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK1.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.9 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES30.2 ft. FS - Fracture Spiral, from 03 to 08 o'clock, within 8 inches of joint: YES58.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES95.1 ft. TFB - Tap Factory Made Abandoned, at 09 o'clock, -, within 8 inches of joint: NO, 6"113.2 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: NO, 6"119.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO164.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"168.2 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES196.3 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES217.6 ft. TFB - Tap Factory Made Abandoned, at 03 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"239.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES240.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"242 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES243 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 4"252.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES309.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"314.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES330.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start332.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"344.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start346.9 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO352.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start354.9 ft. MWL - Water Level, 5 %of cross sectional area354.9 ft. AMH - Downstream Manhole, Survey Begins - 29 0742354.9 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (13)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO

    8 ft. - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    24.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    26.3 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    102.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    112.9 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    158.6 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    186.7 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO

    235.2 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    296.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 03 to 08 o'clock, within 8 inches of joint: YES

    324.7 ft. - Fracture Spiral, from 03 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    348 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
259.8TFB
0MWL
353SAM
24.3DAGS
354.9AMH29 0743
112.9FL
324.7FS
235.2FL
137.3TFB
348FM
45.6TB
2SAP
353DAGS
26.3FL
22.8TF
158.6FM
353SAP
102.6FL
10.4SAM
186.7FM
0AMH29 0742
114.3TF
354.9MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
134.3TB
115.3FL
190.8TF
40.5TFC
8FC
111.9TB
296.6FL
241.7TFB

Properties (7)

additional_info
630074111221062
custom_field_three
FRACTURES, AGGREGATE MISSING
custom_field_two
2`
customer
1
datetime
2021-11-12T08:51:36-08:00
documentation
PROPIPE
is_lateral_inspection
false