- Date
- 11/17/2021
- W/O
- 921558
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00821
- PipeID
- P17120
- Time
- 1:40 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9542
- Sewer Name
- 22 PUDDINGSTONE TRUNK, SECTS 1&2
- City
- SAN DIMAS
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- RFIR_WO_921558_TV22185_NOV2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 12 in.
- Upstream MH
- 22 0761
- Downstream MH
- 22 0762
- Dir. of Survey
- Upstream
- Length Surveyed
- 336.9 ft.
- Total Length
- 336.9 ft.
- Structural Index
- 2
- Structural Quick
- 3122
- Structural Rating
- 7
- O&M Index
- 2
- O&M Quick
- 2L11
- O&M Rating
- 135
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 142
Pipe schematic from manhole 22 0761 to 22 0762 Observation photos (6)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

49.8 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR

67.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: NO

67.1 ft. - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES

248.6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: NO

336.9 ft. - General Observation - COCKROACHES IN MANHOLE