Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2021, 08:45 AM
  • 22 0761_22 0760_11172021_010641.mp4

Date
11/17/2021
W/O
921558
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00821
PipeID
P17119
Time
12:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9542
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_921558_TV22185_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0761
Downstream MH
22 0760
Dir. of Survey
Downstream
Length Surveyed
355.2 ft.
Total Length
355.2 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
201
O&M Index
2
O&M Quick
2M11
O&M Rating
141
Overall Index
2
Overall Quick
Overall Rating
342
Pipe schematic from manhole 22 0761 to 22 0760
MH: 22 0761MH: 22 0760downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 07610 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start16.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES23.5 ft. RFJ - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR23.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"54 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"102.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"201.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"345 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"347.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"353.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish355.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE355.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0760355.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    16.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR

    23.5 ft. - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    355.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (26)

DistanceCodeObservation
2DAGS
255.6TFC
355.2MGOCOCKROACHES IN MANHOLE
355.2AMH22 0760
153.2TFC
0MWL
353.8CM
304.2TFC
102.4TFC
54TFC
23.5RFJ
252.5TFC
0AMH22 0761
201.5TFC
0MWM
99.5TFA
50.3TFC
306.7TFC
204TFC
23.5CM
345TFC
150.6TFC
353.8DAGS
16.5CM
355.2MGOCONNECTION AT MH 3 O'CLOCK
347.4TFC

Properties (7)

additional_info
630069111621203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-11-17T00:45:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false