Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2021, 06:47 AM
  • 22 0708_22 0707_11172021_230021.mp4

Date
11/17/2021
W/O
921733
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00826
PipeID
P17061
Time
10:47 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9601
Sewer Name
22 SAN DIMAS CONNECTION EXTENSION TRUNK
City
SAN DIMAS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_921733_TV22167_NOV2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0708
Downstream MH
22 0707
Dir. of Survey
Downstream
Length Surveyed
355.5 ft.
Total Length
355.5 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
353
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
493
Pipe schematic from manhole 22 0708 to 22 0707
MH: 22 0708MH: 22 0707downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 07080 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"27.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES84.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"353.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0707355.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    27.3 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    355.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
2SAP
2DAGS
184.4TFC
0MWL
355.5AMH22 0707
23.3TFC
0AMH22 0708
27.3FL
353.5DAGS
236.1TFC
353.5SAP
2SSS
355.5MGOCOCKROACHES IN MANHOLE
84.5TFC
0MWM
353.5SSS
0MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
630069111721201
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-11-17T22:47:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false