Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2021, 07:09 PM
  • 18 1189_18 1188_11152021_113155.mp4

Date
11/15/2021
W/O
916676
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00710
PipeID
P14961
Time
11:09 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9281
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 2E&2F
City
WHITTIER
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_916676_TV18111_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 1189
Downstream MH
18 1188
Dir. of Survey
Downstream
Length Surveyed
410.5 ft.
Total Length
410.5 ft.
Structural Index
4
Structural Quick
4333
Structural Rating
21
O&M Index
1
O&M Quick
1800
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
29
Pipe schematic from manhole 18 1189 to 18 1188
MH: 18 1189MH: 18 1188downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 11897.5 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES7.5 ft. MGO - General Observation - STAINING THROUGHOUT12.3 ft. FS - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES12.3 ft. LL - Alignment Left, 10 %, Start14.4 ft. FM - Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES36 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES39.4 ft. FM - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES50.8 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES50.8 ft. LL - Alignment Left, 10 %, Finish410.5 ft. AMH - Downstream Manhole, Survey Ends - 18 1188

Observation photos (6)

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

    7.5 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    12.3 ft. - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    14.4 ft. - Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    36 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    39.4 ft. - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    50.8 ft. - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
50.8FS
12.3FS
14.4FM
0MWM
7.5FS
12.3LL
410.5AMH18 1188
0MWL
36FM
50.8LL
0AMH18 1189
39.4FM
7.5MGOSTAINING THROUGHOUT

Properties (8)

additional_info
630074111521061
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2021-11-15T11:09:26-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30725