Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2021, 06:57 AM
  • 05 0927_05 0926_12142021_230859.mp4

Date
12/14/2021
W/O
926578
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00547
PipeID
P06159
Time
10:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9566
Sewer Name
05 120TH STREET EXTENSION TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_926578_TV05372_DEC2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0926
Downstream MH
05 0927
Dir. of Survey
Upstream
Length Surveyed
338.5 ft.
Total Length
338.5 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
335
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
335
Pipe schematic from manhole 05 0926 to 05 0927
MH: 05 0926MH: 05 0927upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 092714 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"68.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"222.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"274.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"325.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"336.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start336.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start338.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK338.5 ft. MWL - Water Level, 10 %of cross sectional area338.5 ft. MWM - Water Mark, 15 %of cross sectional area338.5 ft. AMH - Downstream Manhole, Survey Begins - 05 0926

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWL
269.8TFC
167.6TFC
338.5SAV
324.5TFC
64TFC
338.5SSS
116.4TFC
2.3SAV
13.4TFC
2.3SSS
0MWM
0AMH05 0926
0.1MGOCONNECTION AT THE MH 9 OC'LOCK
338.5AMH05 0927
219.1TFC

Properties (7)

additional_info
630074121421201
custom_field_three
SURFACE SPALLING AGGREGATE VISIBLE
custom_field_two
2
customer
1
datetime
2021-12-14T22:57:26-08:00
documentation
PROPIPE
is_lateral_inspection
false