Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2021, 11:40 AM
  • 02 0164_02 0163_11102021_035555.mp4

Date
11/10/2021
W/O
922048
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02467
Time
3:40 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9534
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_922048_TV02327_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 0164
Downstream MH
02 0163
Dir. of Survey
Downstream
Length Surveyed
328 ft.
Total Length
328 ft.
Structural Index
2
Structural Quick
312F
Structural Rating
73
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
73
Pipe schematic from manhole 02 0164 to 02 0163
MH: 02 0164MH: 02 0163downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01640 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK4.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES19.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start101.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish212.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"242.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES328 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED328 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED328 ft. AMH - Downstream Manhole, Survey Ends - 02 0163

Observation photos (3)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    4.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    19.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    316.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
328MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
104.2TF
316.2CL
4.9FL
174.1TFC
0MWL
242.8TFC
101.7TF
328MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
187.4CL
0AMH02 0164
156.6TFC
212.8TF
328AMH02 0163
19.5CL
0MWM
159.1TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
216.2TF

Properties (7)

additional_info
630074110921205
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-11-10T03:40:51-08:00
documentation
PROPIPE
is_lateral_inspection
false