Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2021, 10:44 AM
  • 05 0818_05 0817_12132021_025946.mp4

Date
12/13/2021
W/O
921866
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00419
PipeID
P06048
Time
2:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9563
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_921866_TV05374_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
05 0818
Downstream MH
05 0817
Dir. of Survey
Downstream
Length Surveyed
246.5 ft.
Total Length
246.5 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
111
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
111
Pipe schematic from manhole 05 0818 to 05 0817
MH: 05 0818MH: 05 0817downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 08183.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish124.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218.8 ft. FM - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES219.9 ft. B - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES224.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"227.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0817246.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    137.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

    218.8 ft. - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

    219.9 ft. - Broken, from 07 to 02 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0MWL
0MWM
127.2TFC
3.6CM
124.5TFC
137.1CM
70.2TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
246.5AMH05 0817
94.8CM
219.9B
218.7CM
218.8FM
227.4TFC
72.9TFC
174.9TFC
177.6TFC
24.9TFC
246.5MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH05 0818
224.9TFC
22.2TFC

Properties (7)

additional_info
630074121321002
custom_field_three
FRACTURE/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2021-12-13T02:44:21-08:00
documentation
PROPIPE
is_lateral_inspection
false