Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2021, 09:56 AM
  • 01 0779_G 0154_11032021_021115.mp4

Date
11/03/2021
W/O
921616
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00892
PipeID
P01478
Time
2:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9525
Sewer Name
01 BULLIS ROAD TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_921616_TV01203_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
48 in.
Upstream MH
01 0779
Downstream MH
G 0154
Dir. of Survey
Downstream
Length Surveyed
188.9 ft.
Total Length
188.9 ft.
Structural Index
4
Structural Quick
4G00
Structural Rating
152
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
152
Pipe schematic from manhole 01 0779 to G 0154
MH: 01 0779MH: G 0154downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 07792.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"19.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"22.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"66 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.6 ft. D - Deformed, 10 %99.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish188.9 ft. AOC - Drop Connection, Survey Ends - G 0154

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    22.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deformed, 10 %

    86.6 ft. - Deformed, 10 %

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    152.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (17)

DistanceCodeObservation
18.1TFC
0MWM
119.9TFC
66TFC
86.6D
168.9TFC
188.9FM
19.8TFC
152.7TB
2.6FM
0MWL
99.6TF
69.1TFC
147.3TFC
188.9AOCG 0154
22.4TB
0AMH01 0779

Properties (7)

additional_info
630074110221205
custom_field_three
MULTIPLE LARGE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-03T02:56:13-07:00
documentation
PROPIPE
is_lateral_inspection
false